Capacitor group infrared temperature measurement

I. Management regulations

        The infrared thermal imaging method of the parallel capacitor bank is implemented in accordance with UL/T 664-2008 "Infrared Diagnostic Application Specification for Live Equipment".

        Second, the diagnostic criteria

Table 3-17-1 Diagnostic criteria for current heating type equipment defects

Equipment category and location

Thermal image feature

Fault characteristics

Defect property

Handling suggestions

General defect

Serious flaws

Critical defect

Capacitor

Fuse

Taking the capacitive side of the middle of the fuse as the hottest thermal image

Fuse capacity is not enough

The temperature difference does not exceed 10K, and the requirements for important defects are not met.

Hot spot temperature > 55 ° C or б ≥ 80%

Hot spot temperature > 80 ° C or б ≥ 95%

Check fuse

Fuse holder

The fuse holder is the hottest thermal image

Poor contact between fuse and fuse holder

The temperature difference does not exceed 10K, and the requirements for important defects are not met.

Hot spot temperature > 55 ° C or б ≥ 80%

Hot spot temperature > 80 ° C or б ≥ 95%

Check fuse

Laser Radar

Laser radar contains LSPD safety laser scanner and LS laser radar. LSPD safety laser scanner is type 3 with CE certificate. It can be used for agv safety and industrial area protection. LS laser radar is for agv guide. Many famous agv manufacturers has installed LS laser radar to guide their agvs. Our cooperating brand contains Quicktron, Mushiny, Aresbots, etc. Feedback from customers are quite posotive.